LESSON 03.1
Single and dual capacitors: identify before connecting
Capacitance is expressed in farads; these components usually use µF, microfarads. Hz indicates frequency. The nameplate AC voltage is another component characteristic. Start and run capacitors have different functions and operating conditions.
In a dual capacitor, C is common to its two sections, HERM identifies the compressor section and FAN the fan section. Read the markings and trace each conductor on the model diagram; do not infer connections from color, tab count or position. Capacitor C does not automatically connect to compressor C.
Study capacitance measurement with the component isolated, de-energized and stored energy controlled according to the procedure. Check C–HERM and C–FAN separately against rating, tolerance and instrument accuracy. Short-circuit discharge is not taught.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Dual capacitor: C, HERM and FAN
TEMCo RC0102: 35/5 µF, ±5%. Two sections share C. Select a section to measure µF in this isolated, discharged virtual model. Hz is frequency, not capacitance.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Internally joins both sections. It does not automatically mean neutral or the compressor C terminal.
C–HERM · 35 µF ±5% · Section interval: 33.25–36.75 µF. Hypothetical reading: 35.00 µF. Reading within nominal tolerance. Also consider accuracy and procedure; this does not certify the capacitor.
Think before continuing
Does a 35 + 5 µF label mean measuring 40 µF between C and HERM?
Show explanation
No: there are two sections. In this example, C–HERM corresponds to 35 µF and C–FAN to 5 µF. Evaluate them separately using the nameplate tolerance.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
Check your understanding
What information is missing if someone asks for “a capacitor the same size”?
View the explained answer
Function, µF for each section, tolerance, allowed voltage and frequency, terminals and equipment approval; physical size is not enough.
LESSON 03.2
Magnetic contactors: ratings, contacts and coil
A contactor separates control from load. In the referenced families, L identifies line, T load and A1/A2 the coil. Pole counts and auxiliary contacts vary. FLA, LRA and resistive-load ratings are different specifications; select for the application and exact coil, including AC/DC and frequency.
To study continuity of contacts normally operating at line voltage, the example is first fully de-energized and isolated. Check each pole in its defined states. An NO contact that stays closed at rest needs investigation; a beep alone does not evaluate loaded voltage drop or insulation.
Check coil resistance in Ω using its part number and procedure. OL can indicate an open circuit; a finite reading does not rule out shorted turns or actuation problems. There is no universal resistance range, and AC coil current is not calculated from V/R alone.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Contactor: poles and coil
Ideal two-pole NO contactor. The drawing changes position without energizing real equipment. L/T identify power terminals; A1/A2 identify the coil.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Check continuity without voltage and with the component isolated. An NO pole opens at rest and closes when operated in this example.
L1–T1: Open · L2–T2: Open. DE-ENERGIZED · ISOLATED COMPONENT
Think before continuing
Is a higher-amp contactor always a suitable replacement?
Show explanation
No. Check poles, load application, FLA/LRA, voltage, AC/DC coil and frequency, auxiliary contacts and equipment approval.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
Check your understanding
What does continuity between L1 and T1 prove with a closed pole?
View the explained answer
That an electrical path exists under those test conditions. It does not certify the complete contactor or its operating capability.
LESSON 03.3
Compressors: function and motor families
The compressor raises vapor pressure in the refrigerant circuit. Diagnosis combines electrical, refrigeration, control and mechanical evidence. One winding-resistance or current reading cannot establish the entire compressor’s condition.
In the displayed single-phase model, C is common, R run and S start: C–R and C–S are the two windings; R–S traverses them in series. Check actual values and terminal positions in the manual. An open thermal protector can affect readings. Insulation tests require the manufacturer’s method.
A three-phase or inverter-driven compressor needs its own identification and procedure; do not impose the C/R/S drawing on it. Do not apply an insulation test through connected electronics.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Single-phase compressor: C, R and S
Teaching equivalent of two single-phase windings, without a supply. It does not apply directly to three-phase or inverter compressors.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
This is the common point of the displayed windings. Confirm physical C/R/S locations with the manufacturer.
C–R = 1 Ω. Hypothetical winding values; not a compressor specification.
Think before continuing
If C–R = 1 Ω and C–S = 2 Ω in this example, what do you expect between R and S?
Show explanation
Approximately 3 Ω, accounting for lead and connection effects. This sum does not prove correct insulation or compressor mechanical health.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
Check your understanding
Does the correct resistance sum rule out a mechanical fault?
View the explained answer
No. It only checks a circuit relationship under the measurement conditions; the other specified checks are still needed.
LECCIÓN 03.4
Temperature sensors: type, curve and context
NTC resistance falls as temperature rises; PTC resistance rises within its operating range. The graphic uses typical points from two identified CAREL references with their units. It does not treat every sensor as “10 kΩ”.
Interpret readings using actual temperature, isolated sensor resistance, the correct table and tolerance. Also check the signal or input expected by the controller. RTDs, thermocouples and active sensors use other principles; continuity does not prove accurate measurement.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Temperature and resistance: NTC / PTC
Three typical CAREL points: NTC 10 kΩ / β3435 and PTC KTY81/121. These are not a universal table or acceptance limits.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
NTC resistance decreases as temperature rises. PTC resistance increases, within its operating range.
NTC 10 kΩ / β3435 · 25 °C → 10000 Ω. Typical CAREL reference value; check the installed sensor table and tolerance.
Think before continuing
Do all “10 kΩ” sensors have the same curve?
Show explanation
No. That rating needs a reference temperature; curve, tolerance and controller compatibility also matter.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
Check your understanding
A sensor reads 10 kΩ. Do we now know its temperature?
View the explained answer
Only if its type, curve and conditions are known. For the example NTC it is the typical value at 25 °C; it is not a rule for every sensor.
LECCIÓN 03.5
Normally open and normally closed
NO and NC describe contacts relative to a reference condition. For a relay it is usually the de-energized coil; for pressure controls, check how the manufacturer represents pressure and actuation. Actual state may differ from the drawn normal state.
A permission circuit may include several contacts: if one opens, that path is interrupted. Before attributing a fault, identify its actuating variable and whether opening is a valid protective response. Never bypass safety to turn a study result into an operating command.
THEORY → DIAGRAM → VIRTUAL PRACTICE
NO and NC: the reference state
NO = normally open; NC = normally closed, relative to a defined reference state. They do not mean “equipment running” or “equipment faulty”.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
In this example it is open when not actuated and closed when actuated.
NO: Open · NC: Closed.
Think before continuing
Does an NC contact always have continuity?
Show explanation
No. It describes its normal reference state; it may open when actuated.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
Check your understanding
Does “normally closed” mean “never opens”?
View the explained answer
No. It can open when actuated. Interpret the reference state and device sequence.
LECCIÓN 03.6
High and low pressure: switch or transducer
A pressure switch changes contacts at defined conditions. High and low pressure do not share universal settings: cutoff, differential and reset depend on product code and application. A protective shutdown does not prove a faulty pressure switch.
A transducer provides a pressure-related signal. The AKS 32R example is ratiometric: with a nominal 5 V DC supply it provides 0.5–4.5 V DC between its range endpoints. Signal-to-pressure conversion requires the exact range; do not test it as a contact or apply 24 V by analogy with other controls.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Pressure switch and transducer: two signals
Choose contact-based permission or an analog signal. Physical pressure and electricity are different domains.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Protection responds to the manufacturer-defined condition. This example opens permission on high pressure; it sets no cutoff pressure.
Permission path closed in this example.
Think before continuing
Is an active transducer diagnosed like a switch?
Show explanation
No. Identify its supply, output, range and exact procedure. Do not bypass safeties to force equipment operation.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
Check your understanding
Does an open protective device justify bypassing it?
View the explained answer
No. First identify the condition that caused opening and follow the equipment procedure.
LECCIÓN 03.7
24 V control transformers
A transformer has primary and secondary windings; in this example they are separate circuits and energy transfer is magnetic. Nominal output is 24 V AC. The nameplate defines voltages, frequency and VA rating; do not change taps or assume compatibility from appearance.
The TR40VA002US datasheet specifies 40 VA with a 24 V AC secondary. The nominal quotient is approximately 1.67 A. Actual selection considers simultaneous loads, inrush, temperature and specified protection. Winding continuity does not prove correct turns ratio or insulation.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Transformer: 24 V AC and VA rating
TR40VA002US nominal example: 120 V AC primary, 24 V AC secondary, 40 VA. The exercise adds loads; it does not size protective devices.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Receives the specified voltage and frequency. Taps and colors depend on the model.
Hypothetical load: 24 VA / 24 V = 1.00 A. Nominal rating: 40 VA / 24 V ≈ 1.67 A. Within the nominal 40 VA; inrush and conditions still need checking. This calculation does not select the fuse.
Think before continuing
Is a 48 VA load within a 40 VA nominal rating?
Show explanation
No. It exceeds the example rating. Even below 40 VA, inrush, conditions and approved selection need checking.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
Check your understanding
Does 40 VA / 24 V automatically determine the fuse to install?
View the explained answer
No. It is a nominal relationship; protection comes from the applicable specification.
LECCIÓN 03.8
Fuses: recognize an opening and its cause
A fuse interrupts the circuit under the conditions of its time-current characteristic. Study resistance checks with it isolated and de-energized. An open-circuit reading alone does not explain why it opened.
Replacement requires suitable current, applicable AC/DC voltage, class, interrupting rating and timing behavior. Interrupting rating is not operating amperage. Investigate overcurrent or faults according to the procedure; never bypass or oversize to prevent opening.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Fuse: continuity and selection
Isolated, de-energized component. Recognizing an open circuit is different from choosing a suitable fuse.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
An open element interrupts the electrical path. An isolated test avoids mistaking parallel paths for fuse continuity.
Continuous path · DE-ENERGIZED · ISOLATED COMPONENT. Continuity does not confirm class, interrupting rating or cause of failure.
Think before continuing
Are two fuses with the same amperage necessarily equivalent?
Show explanation
No. Other application and manufacturer requirements must match. Also investigate why the original opened.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
Check your understanding
Is a fuse compatible just because it fits the holder?
View the explained answer
No. Size and amperage do not replace checking all required characteristics.
LECCIÓN 03.9
Solenoid valves: electrical control and fluid circuit
The coil actuates a mechanism controlling fluid passage. NC and NO are defined relative to the de-energized coil. Identify the exact body and coil: voltage, AC/DC, frequency, refrigerant, pressure, temperature and allowed direction.
Evaluate coil resistance de-energized using its reference. In a pilot-operated valve, opening can also depend on pressure differential. Neither a click nor an Ω reading alone proves correct flow. Stepper-motor electronic expansion requires another method.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Solenoid valve: coil and fluid passage
Ideal functional model. Pilot-operated valves may require pressure differential; an energized coil does not guarantee flow.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Identify AC/DC voltage, frequency and compatibility. Evaluate resistance without voltage using the manufacturer reference.
Ideal closed position; not a tightness test.
Think before continuing
Does hearing a click prove that correct flow is passing?
Show explanation
No. Verify circuit conditions and response using the model procedure.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
Check your understanding
Does an energized coil guarantee correct opening of a pilot-operated valve?
View the explained answer
No. That model’s fluid, refrigeration and mechanical conditions must also be met.
LECCIÓN 03.10
Dampers with motors and gears
An actuator converts a command into motion through a motor, gears and shaft coupling. Distinguish supply, command signal and feedback where present. There are on/off, floating and proportional versions; they do not all use the same range.
The LF24-SR US example uses a 24 V AC/DC supply and control configured for 2–10 V DC. In the ideal model, 6 V is mid-travel, not half the airflow. Its spring returns to a safety position on power loss; the end stop depends on mounting. Motorized return requires energy and is a different architecture.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Damper: signal, gears and position
LF24-SR US reference: 24 V AC/DC supply, 2–10 V DC control and spring return. Displayed position is an ideal relationship, not an airflow measurement.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
The command signal does not replace the supply. Other models use on/off, floating control or different ranges.
6 V CC/DC → Ideal travel: 50.0 %. Percentage of travel, not airflow.
Think before continuing
Does 50% actuator travel mean 50% airflow?
Show explanation
No. Airflow depends on the damper, pressure and system. Verify actual position and performance separately.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
Check your understanding
The controller requests opening, but motion is not confirmed. Which elements do you distinguish?
View the explained answer
Supply, signal, configuration, actuator, coupling, travel and damper motion; check them according to the manual without assuming which one is the cause.
Sources for further study
- TEMCo · Dual run capacitor selection guide ↗
- TEMCo RC0102 · 35/5 µF, ±5% ↗
- Fluke · Measuring capacitance ↗
- Fluke · Continuity testing ↗
- Schneider Electric · 8910 definite-purpose contactors ↗
- Schneider Electric · A1 / A2 ↗
- Schneider Electric · L / T terminals ↗
- Schneider Electric · Coil resistance by part number ↗
- Copeland · AE-102, compressor motor circuits ↗
- CAREL · Passive probes +030220655, sections 5.1 / 12.3 ↗
- Danfoss · KP / RT pressure controls ↗
- Danfoss · AKS 32R / 2050 pressure transmitters ↗
- Functional Devices · TR40VA002US ↗
- Eaton · Fuse technology ↗
- Danfoss · EVR 2–40 v2 ↗
- Belimo · LF24-SR US ↗
Reference readings: some resources are in English. Consult the current equipment manual before any work. Access to restricted documentation is not assumed.