Learn with interactive diagrams

Trace the path, identify each component and test an idea. Start with symbols and circuits, then explore refrigeration, measurements and complex systems.

1. Read the theory. 2. Select components. 3. Change one condition. 4. Explain the result before opening the answer.

How to read the drawings and their references

Circuit symbols and functional blocks are identified in each drawing. IEC 60617 addresses electrical symbols; ISO 14617-2:2025 addresses industrial symbols and refers electrical symbols to IEC. A standard does not automatically certify an educational drawing.

Electrical conventions: IEC 60617; shapes checked against Eaton, chapter 9. Refrigeration drawings are functional diagrams based on manufacturer documentation. These drawings are not claimed to be IEC/ISO certified.

References reviewed: October 20, 2026.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Read an electrical schematic

Recognize a junction, resistor, capacitor and contact before tracing a circuit.

Circuit symbols
Read an electrical schematicRecognize a junction, resistor, capacitor and contact before tracing a circuit. Junction → Resistor R → Capacitor C → Contact S → Motor M → Diode DJunctionResistor RCapacitor CContact SMMotor MAKDiode D

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Think before continuing

Does a crossing without a dot always connect two wires?

Show explanation

No. In this legend, only a dot indicates a junction. Check each document’s convention.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Series and parallel: see Ohm’s law

Ideal virtual resistive circuit at 24 V DC. Change the topology and R1; compare current, voltage and equivalent resistance.

Circuit symbols
Series and parallel: see Ohm’s lawIdeal virtual resistive circuit at 24 V DC. Change the topology and R1; compare current, voltage and equivalent resistance. 24 V DC source → Resistor R1 → Resistor R2+−24 V DCR1 12 ΩR2 24 ΩSeries · I = 0.67 A · Req = 36.00 Ω

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Equivalent resistance: 36.00 Ω · Total current: 0.67 A. R1: 8.00 V / 0.67 A. R2: 16.00 V / 0.67 A. Ideal resistive model; does not represent an AC motor.

Think before continuing

With R1 = 12 Ω and R2 = 24 Ω, which connection draws more source current?

Show explanation

Parallel: Req = 8 Ω and I = 3 A. In series: Req = 36 Ω and I ≈ 0.67 A. These are ideal resistors, not an AC motor calculation.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

One quantity, one connection

Explore conceptual meter placement in an ideal circuit. Real equipment measurements require trained personnel and a suitable instrument.

Circuit symbols
One quantity, one connectionExplore conceptual meter placement in an ideal circuit. Real equipment measurements require trained personnel and a suitable instrument. Source → 12 Ω load → Meter+−24 V DC12 ΩV

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Voltmeter in parallel: 24 V DC

Think before continuing

Does a continuity beep prove that a component is exactly 0 Ω?

Show explanation

No. It indicates a condition relative to the instrument threshold. Read the value and consult its manual.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Control and power: a relay

Two separate circuits. The coil operates a contact through a mechanical link; there is no wire between those functions.

Circuit symbols
Control and power: a relayTwo separate circuits. The coil operates a contact through a mechanical link; there is no wire between those functions. Control contact → Coil K1 → Contact K1 (NO) → Load MControlLoad+−K1+−MMechanical link24 V DC24 V DC

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Coil at rest; NO contact open.

Think before continuing

Is the dashed line between coil and contact a conductor?

Show explanation

No: it represents mechanical actuation. The electrical circuits remain separate.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

AC → DC → variable AC

Blocks in a typical electronic conversion. This is not a circuit-board schematic or a terminal map.

Functional diagram
AC → DC → variable ACBlocks in a typical electronic conversion. This is not a circuit-board schematic or a terminal map. Rectifier → DC bus → Inverter → MotorCA / ACRectifierDC busInverterMTypical conversion; functional blocks, not terminals.

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Think before continuing

Are mains Hz enough to know inverter compressor speed?

Show explanation

No. The output stage and controller regulate the motor. Consult the manufacturer’s variables and methods.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

The refrigerant path

Vapor-compression cycle in cooling mode. Pressure, phase and heat transfer are different concepts.

Functional diagram
The refrigerant pathVapor-compression cycle in cooling mode. Pressure, phase and heat transfer are different concepts. Compressor → Condenser → Expansion → EvaporatorCompressorCondenserExpansionEvaporatorVapor · highLiquid · highMixture · lowVapor · lowReleases heatAbsorbs heat

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Think before continuing

Does the entire low-pressure path contain only vapor?

Show explanation

No: there is a liquid/vapor mixture after expansion. Low pressure does not imply a single phase.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Cooling and heating: roles change

Compare exchanger roles. The reversing valve changes connections; the compressor does not pump backward.

Functional diagram
Cooling and heating: roles changeCompare exchanger roles. The reversing valve changes connections; the compressor does not pump backward. Indoors → Cycle reversal → OutdoorsIndoorsCycle reversalOutdoorsEvaporatorCondenserAbsorbs heatReleases heatHeat

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Heat exchange changes; valve piping is not shown.

Think before continuing

Does switching to heating reverse compressor pumping direction?

Show explanation

No. Connections and exchanger roles change; suction and discharge retain their functions.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Return air, supply air and ventilation

Functional air path. Actual fan, filter and coil positions depend on the design.

Functional diagram
Return air, supply air and ventilationFunctional air path. Actual fan, filter and coil positions depend on the design. Return → Filter → Coil → FanReturnFilterCoilFanRoomSupplyRecirculation only in this example.

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Recirculation only in this example.

Think before continuing

If the fan runs, do we know that fresh air is entering?

Show explanation

No. Toggle the drawing’s outdoor inlet: recirculation can operate without outdoor ventilation.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Saturation, superheat and subcooling

R-454B: real Honeywell chart points and hypothetical pipe temperatures. These are exercises, not target charging pressures or temperature differences.

Functional diagram
Saturation, superheat and subcoolingR-454B: real Honeywell chart points and hypothetical pipe temperatures. These are exercises, not target charging pressures or temperature differences. Pressure and P–T table → Pipe temperature → Temperature difference110 psigDew: 41.1 °FVapor55.1 °FSH = 14.0 °F

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

R-454B · 110 psig · Dew 41.1 °F. SH = 55.1 − 41.1 = 14.0 °F (7.8 °C). Pipe temperature chosen for the exercise; not an adjustment target.

Think before continuing

For R-454B, do SH and SC use the same saturation column?

Show explanation

No. Dew point for superheat; bubble point for subcooling. Do not apply this chart to R-410A or R-32.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Vacuum: measure the isolated system

Example criterion: Lennox EL16KC1, page 23, no rise above 500 microns during 20 minutes of isolation. Always check the model procedure.

Functional diagram
Vacuum: measure the isolated systemExample criterion: Lennox EL16KC1, page 23, no rise above 500 microns during 20 minutes of isolation. Always check the model procedure. System → Vacuum gauge → Isolation → Vacuum pumpSystemVacuum gaugeIsolationPumpPump isolated50040004305450104601546020Time (min)Absolute pressure (microns)

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

This hypothetical record meets the stated 500-micron / 20-min criterion. Exercise curves, connected by segments; not real measurements.

Think before continuing

Is reaching 400 microns with the pump running enough to pass this criterion?

Show explanation

No. The isolation period is also evaluated. These two records are exercises, not real equipment results or a universal proof of no leaks.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Chiller: circuits that do not mix

Follow energy from the building through the refrigerant to outdoors. Heat-transfer lines are not pipes connecting fluids.

Functional diagram
Chiller: circuits that do not mixFollow energy from the building through the refrigerant to outdoors. Heat-transfer lines are not pipes connecting fluids. Chilled water → Refrigerant → Outdoor heat rejectionChilled waterLoadRefrigerantEvaporatorCondenserQCondenser waterTowerQQ = Heat

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Three separate circuits; they only exchange heat.

Think before continuing

Does chilled water mix with refrigerant in the evaporator?

Show explanation

No. They exchange energy through heat-exchanger surfaces while remaining separate.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

VRF: one network, several zones

Conceptual network: each line represents a circuit relationship, not the number of pipes. Communication is shown separately.

Functional diagram
VRF: one network, several zonesConceptual network: each line represents a circuit relationship, not the number of pipes. Communication is shown separately. Outdoor unit → Zone 1 → Zone 2 → CommunicationOutdoor unitZone 1Zone 2CommunicationRefrigerant connectionControl signal

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Think before continuing

Does every VRF allow simultaneous cooling and heating?

Show explanation

No. It must be a heat-recovery variant with an approved configuration. Check the model.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

From measurement to response

Functional control loop. Select a stage and explain what evidence you would need before attributing a fault to it.

Functional diagram
From measurement to responseFunctional control loop. Select a stage and explain what evidence you would need before attributing a fault to it. Sensor → Controller → Actuator → ProcessSensorControllerActuatorProcessControl signal

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Think before continuing

Does a sensor alarm prove it needs replacement?

Show explanation

No. Conditions, signal and connections are checked according to the manufacturer’s procedure.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Marine AC: water and refrigerant separated

Functional seawater path in an MCS system. It does not represent heights, mounting positions or an installation plan.

Functional diagram
Marine AC: water and refrigerant separatedFunctional seawater path in an MCS system. It does not represent heights, mounting positions or an installation plan. Water intake and strainer → Water pump → Heat exchanger → Water dischargeIntake / strainerWater pumpHeat exchangerWater dischargeRefrigerantSeawaterHeat-transfer wall

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Think before continuing

Does seawater enter the refrigerant piping?

Show explanation

No. Both fluids remain separated by the heat exchanger.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Dual capacitor: C, HERM and FAN

TEMCo RC0102: 35/5 µF, ±5%. Two sections share C. Select a section to measure µF in this isolated, discharged virtual model. Hz is frequency, not capacitance.

Circuit symbols
Dual capacitor: C, HERM and FANTEMCo RC0102: 35/5 µF, ±5%. Two sections share C. Select a section to measure µF in this isolated, discharged virtual model. Hz is frequency, not capacitance. C · capacitor common → HERM · compressor section → FAN · fan sectionDE-ENERGIZED · ISOLATED COMPONENTCHERMFAN35 µF5 µFC–HERM: 35.0 µFCapacitor C ≠ compressor CµF

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

C–HERM · 35 µF ±5% · Section interval: 33.25–36.75 µF. Hypothetical reading: 35.00 µF. Reading within nominal tolerance. Also consider accuracy and procedure; this does not certify the capacitor.

Think before continuing

Does a 35 + 5 µF label mean measuring 40 µF between C and HERM?

Show explanation

No: there are two sections. In this example, C–HERM corresponds to 35 µF and C–FAN to 5 µF. Evaluate them separately using the nameplate tolerance.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Contactor: poles and coil

Ideal two-pole NO contactor. The drawing changes position without energizing real equipment. L/T identify power terminals; A1/A2 identify the coil.

Circuit symbols
Contactor: poles and coilIdeal two-pole NO contactor. The drawing changes position without energizing real equipment. L/T identify power terminals; A1/A2 identify the coil. Pole L1–T1 → Pole L2–T2 → Coil A1–A2DE-ENERGIZED · ISOLATED COMPONENTL1L2T1T2A1A2K1Example NO polesL1–T1: Open · L2–T2: Open

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

L1–T1: Open · L2–T2: Open. DE-ENERGIZED · ISOLATED COMPONENT

Think before continuing

Is a higher-amp contactor always a suitable replacement?

Show explanation

No. Check poles, load application, FLA/LRA, voltage, AC/DC coil and frequency, auxiliary contacts and equipment approval.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Single-phase compressor: C, R and S

Teaching equivalent of two single-phase windings, without a supply. It does not apply directly to three-phase or inverter compressors.

Circuit symbols
Single-phase compressor: C, R and STeaching equivalent of two single-phase windings, without a supply. It does not apply directly to three-phase or inverter compressors. C · motor common → C–R · run winding → C–S · start windingDE-ENERGIZED · ISOLATED COMPONENTCRS1 Ω2 ΩC–R = 1 Ω

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

C–R = 1 Ω. Hypothetical winding values; not a compressor specification.

Think before continuing

If C–R = 1 Ω and C–S = 2 Ω in this example, what do you expect between R and S?

Show explanation

Approximately 3 Ω, accounting for lead and connection effects. This sum does not prove correct insulation or compressor mechanical health.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Temperature and resistance: NTC / PTC

Three typical CAREL points: NTC 10 kΩ / β3435 and PTC KTY81/121. These are not a universal table or acceptance limits.

Circuit symbols
Temperature and resistance: NTC / PTCThree typical CAREL points: NTC 10 kΩ / β3435 and PTC KTY81/121. These are not a universal table or acceptance limits. Sensing element → Resistance and temperature → Control inputCAREL · NTC 10 kΩ / β3435NTC10000 Ω25 °CReferenceResistive sensor

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

NTC 10 kΩ / β3435 · 25 °C → 10000 Ω. Typical CAREL reference value; check the installed sensor table and tolerance.

Think before continuing

Do all “10 kΩ” sensors have the same curve?

Show explanation

No. That rating needs a reference temperature; curve, tolerance and controller compatibility also matter.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

NO and NC: the reference state

NO = normally open; NC = normally closed, relative to a defined reference state. They do not mean “equipment running” or “equipment faulty”.

Circuit symbols
NO and NC: the reference stateNO = normally open; NC = normally closed, relative to a defined reference state. They do not mean “equipment running” or “equipment faulty”. NO contact → NC contact → Device referenceNOOpenNCClosedTwo independent contacts; defined reference state

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

NO: Open · NC: Closed.

Think before continuing

Does an NC contact always have continuity?

Show explanation

No. It describes its normal reference state; it may open when actuated.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Pressure switch and transducer: two signals

Choose contact-based permission or an analog signal. Physical pressure and electricity are different domains.

Functional diagram
Pressure switch and transducer: two signalsChoose contact-based permission or an analog signal. Physical pressure and electricity are different domains. High pressure → Low pressure → Controller signalPermissionControlHighLowClosedClosedPermission path closed in this example.

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Permission path closed in this example.

Think before continuing

Is an active transducer diagnosed like a switch?

Show explanation

No. Identify its supply, output, range and exact procedure. Do not bypass safeties to force equipment operation.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Transformer: 24 V AC and VA rating

TR40VA002US nominal example: 120 V AC primary, 24 V AC secondary, 40 VA. The exercise adds loads; it does not size protective devices.

Circuit symbols
Transformer: 24 V AC and VA ratingTR40VA002US nominal example: 120 V AC primary, 24 V AC secondary, 40 VA. The exercise adds loads; it does not size protective devices. Primary → 24 V AC secondary → Control loadTR40VA002US · 40 VA120 V CA/AC24 V CA/AC24 VAPrimarySecondaryWinding symbol; does not indicate the number of turns.

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Hypothetical load: 24 VA / 24 V = 1.00 A. Nominal rating: 40 VA / 24 V ≈ 1.67 A. Within the nominal 40 VA; inrush and conditions still need checking. This calculation does not select the fuse.

Think before continuing

Is a 48 VA load within a 40 VA nominal rating?

Show explanation

No. It exceeds the example rating. Even below 40 VA, inrush, conditions and approved selection need checking.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Fuse: continuity and selection

Isolated, de-energized component. Recognizing an open circuit is different from choosing a suitable fuse.

Circuit symbols
Fuse: continuity and selectionIsolated, de-energized component. Recognizing an open circuit is different from choosing a suitable fuse. Fuse element → Resistance check → Selection dataDE-ENERGIZED · ISOLATED COMPONENTΩClosedA · V AC/DC · class · interrupting rating

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Continuous path · DE-ENERGIZED · ISOLATED COMPONENT. Continuity does not confirm class, interrupting rating or cause of failure.

Think before continuing

Are two fuses with the same amperage necessarily equivalent?

Show explanation

No. Other application and manufacturer requirements must match. Also investigate why the original opened.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Solenoid valve: coil and fluid passage

Ideal functional model. Pilot-operated valves may require pressure differential; an energized coil does not guarantee flow.

Functional diagram
Solenoid valve: coil and fluid passageIdeal functional model. Pilot-operated valves may require pressure differential; an energized coil does not guarantee flow. Coil → Body and mechanism → Fluid circuitCoil · OFFMechanismNC → ClosedFluid

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Ideal closed position; not a tightness test.

Think before continuing

Does hearing a click prove that correct flow is passing?

Show explanation

No. Verify circuit conditions and response using the model procedure.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

THEORY → DIAGRAM → VIRTUAL PRACTICE

Damper: signal, gears and position

LF24-SR US reference: 24 V AC/DC supply, 2–10 V DC control and spring return. Displayed position is an ideal relationship, not an airflow measurement.

Functional diagram
Damper: signal, gears and positionLF24-SR US reference: 24 V AC/DC supply, 2–10 V DC control and spring return. Displayed position is an ideal relationship, not an airflow measurement. Command and supply → Motor and gears → Damper bladeSupply 24 V AC/DCONY = 6 V CC/DCMotor + gearsDamperIdeal travel: 50.0 %

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

6 V CC/DC → Ideal travel: 50.0 %. Percentage of travel, not airflow.

Think before continuing

Does 50% actuator travel mean 50% airflow?

Show explanation

No. Airflow depends on the damper, pressure and system. Verify actual position and performance separately.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →